Description :
Tenders for Supply Installation, Testing & Commissioning Of Transformer Outdoor Type, 33 Kv/11 Kv, 3- Phase, 50 C/s, Oil Immersed, Naturally Cooled, 1.6 Mva, Core Type, Double Wound With Copper Conductor, Having Off Circuit Taps +5% To -10% In Step Of 2.5% On Hv To Vary Hv, 35/40 Degree Centigrade Temperature Rise In Oil & Winding Respectively, High Voltage Side Connected In Delta Where As Low Voltage Side Connected In Star, Having Vector Group Reference Dy N 11, With Neutral Of The Secondary Winding Brought For Earthing, Outdoor Type, Having Bushings On Hv & Lv Sides, Complete With First Filling Of Oil Complying With Is: 335 And Other Fittings & Accessories As Per Is: 2026 And Other Relevant Applicable Standards. Make- Kirloskar, Abb Or Similar. Is: 1180 (part-i)/2014 Of The Earlier Published Tender May Be Read As Is: 2026 And Other Relevant Applicable Standards In Detailed Specification Attached With Tender (annexure A). [ Warranty Period: 30 Months After The Date Of Delivery ] ]